Single-conductor cables used in portable earthing and bridging devices.
Conductor:
Copper, multi-wire, flexible class 6 (acc. to EN 60228)
Insulation:
General use silicone rubber, type EM 9 (acc. to EN 50363-2-1)
Max. working temperature:
180°C
Cables can be used in overhead and indoor conditions within temperatures from -40°C to 70°C.
Standard: EN 61138
Cables conform to the requirements of REACH Regulation and RoHS Directive.

| Nominal cross-section | Single wire diameter | Resistance at 20°C | Wall insulation thickness | Outer diameter of cable | |
|---|---|---|---|---|---|
| (max.) | (max.) | (nom.) | (min.) | (max.) | |
| mm2 | mm | mΩ/m | mm | mm | |
| 16 | 0,2 | 1,210 | 1,4 | 7,5 | 9,5 |
| 25 | 0,2 | 0,780 | 1,4 | 8,8 | 11,2 |
| 35 | 0,2 | 0,554 | 1,4 | 10,1 | 12,7 |
| 50 | 0,2 | 0,386 | 1,6 | 11,9 | 15,2 |
| 70 | 0,2 | 0,272 | 2,1 | 14,6 | 17,4 |
| 95 | 0,2 | 0,206 | 2,3 | 16,5 | 19,9 |
| 120 | 0,2 | 0,161 | 2,7 | 18,9 | 22,0 |